Customization: | Available |
---|---|
Shell Material: | Stainless Steel |
Voltage Level: | Low Voltage Medium Voltage High Voltage |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ltem | parameter | ltem | parameters |
Rated voltage kV | 24 | Rated short-time frequency withstand voltage (break Port) kV | 79 |
Rated current A | 1250 | Rated lightning impulse withstand voltage (Break Port) peak kV | 145 |
Rated frequency Hz | 50 | Classification level according to mechanical life | M2 |
Rated short-circuit breaking current | 25 | Classification level according to electrical life | E2 |
Rated short-circuit closing current kA Peak |
63 | According to the opening and closing capacity of the capacitive current classification level |
C2 |
Rated short-time withstand current holding Continuous time s | 4 | Rating of auxiliary contacts | 2 |
Rated short-time withstand current kA |
25 | Closing operating voltage V (max. / rated) (fixed/minimum) | AC242/220/1 87 |
Rated peak withstand current kA Peak | 63 | Breakout operating voltage V (max.) (fixed/minimum) | AC242/220/1 43 |
Rated cable charging on/off Stream A | 25 | SF6 gas rated filling pressure (Gauge pressure at 20C) MPa |
0.045 |
Rated line charging on/off Stream A | 10 | SF6 Gas Minimum Functional Pressure (Gauge pressure at 20C) MPa |
0.02 |
Rated short-time frequency withstand Pressure kV | 65 | Rated lightning impulse withstand voltage kV Peak | 125 |